Focus on gas supercharging, liquid supercharging, gas - liquid supercharging technology application
GLTCN
服务热线 0531-85956889
Home » Standard products » Industry -Specific Pump » Fire agent filling pump
Fire agent filling pump
Fire agent filling pump Fire agent filling pump is a pneumatic pump, which is driven by compressed air to pressurize and fill fire agents, and is used for filling, filling, conveying and recovery of HFC-propane, perfluorohexanone and other fire agents.

Fire agent filling pump

Fire agent filling pump is a pneumatic pump, which is driven by compressed air to pressurize and fill fire agents, and is used for filling, filling, conveying and recovery of HFC-propane, perfluorohexanone and other fire agents.

First, product characteristics

It uses pure compressed air as the driving power source, fire agent filling pump as the pressure source, fire agent as the pressurized medium, and the output pressure is proportional to the driving air source pressure. By adjusting the pressure of the driving air source, the corresponding pressure of the pressurized fire agent can be obtained. When the driving air source pressure and pressurized pressure reach a balance, the refrigerant booster pump will stop pressurizing, and the output pressure is stable on the preset pressure. With explosion-proof, energy saving, environmental protection, adjustable output pressure, small volume, light weight, simple operation, reliable performance, wide range of application and so on.

Two, product use

1. Suitable for filling and conveying of HFC-propane, perfluorohexanone and other firefighting agents;

2, suitable for the recovery of HFC-propane, perfluorohexanone and other fire agents;

Three, booster pump composition

The fire agent filling pump is composed of a driving cylinder, a medium booster cylinder, an automatic reversing valve, an inlet and outlet check valve, imported high quality seals, a driving and pressurizing piston, etc. Mature technology, convenient connection and control, compact structure, compact appearance and generous.

Iv. Technical parameters

Driving pressure 2-8bar        pressure range 0-48bar
Supercharging ratio 6:1         Output flow 14L/min
Driving gas inlet size 1/2       booster cylinder diameter 63mm
Medium inlet size ZG1/2       stroke 60mm
Medium outlet size ZG1/2     Noise < 65dB

V. Operation and installation

1. Installation: During installation, please refer to the size of each interface in the technical parameters to avoid foreign matter entering the pump and keep the inlet and outlet clean.